How to read a Borlink™ data sheet

· Basics

A Borlink™ product data sheet is two pages long, and the voltage it names, the test methods, the footnotes and the disclaimer all matter. This guide walks through a current (2026) sheet section by section, using the seven Borlink grades we supply as examples — the XLPE insulation grades LE4244S, LS4201S, LE4244EHV and LS4201EHV, and the semiconductive screen compounds LE0592S, LE0500 and LE0550DC.

Grade facts come from the producer’s sheets; what each test standard covers comes from the official ISO, IEC and ASTM catalogue pages. Both are linked under References.

The header: grade, family and edition

The top line of each sheet carries a date and an edition number, for example “06.03.2026 Ed.4” on LE4244S (day.month.year). The editions we hold are LE4244S Ed.4, LE4244EHV Ed.4, LE0592S Ed.5 and LE0500 Ed.4 (all 6 March 2026), LS4201S Ed.6 and LS4201EHV Ed.3 (5 May 2026), and LE0550DC Ed.1 (7 April 2026). When you compare a sheet with a specification, a COA or an older file, check the edition first.

Under the grade name sits a one-line family label: “Crosslinkable Insulation Compound” on the four insulation grades, “Crosslinkable Semiconductive Compound” on LE0592S and LE0500. The LE0550DC Ed.1 sheet has no such line.

Description: what the grade is for

The Description section says what the compound is and, on most sheets, the intended application. LE4244S is a crosslinkable natural polyethylene (XLPE) compound with “very low sagging properties”, designed for horizontal lines and for thick insulation walls on CCV lines (see sagging). LS4201S is based on Supercure technology, with excellent scorch resistance and a reduced degassing burden. All four insulation sheets say the compound results in superclean cable insulation, with cleanliness assured through the Borealis Quality Management system.

The key sentence states the rated voltage. LE4244S, LS4201S and LE0592S are intended for HV AC cables “with rated voltages up to 230 kV (Um = 245 kV)”; LE4244EHV, LS4201EHV and LE0500 for EHV AC cables “above 230 kV”, each followed by “(Um = 245 kV)”. Every AC sheet adds that the values are voltages between phases as defined in IEC 60183 (Guidance for the selection of high-voltage A.C. cable systems). Our glossary explains Um and HV and EHV; the 110 kV, 220 kV, 330 kV and 500 kV pages map these bands to grades.

The semiconductive sheets also state which screen layers the grade is for. LE0592S, for example, is for the conductor screen and bonded insulation screen, and also the conductor screen of strippable constructions (bonded and strippable screens). LE0550DC is for the semiconductive screens of XLPE HVDC cables and gives no voltage rating.

One quirk: the sheets refer to an “Applications” section, but only LS4201EHV Ed.3 and LE0550DC Ed.1 have that heading. On the other five the application sentence sits under Description.

Specifications: standards, and what the sheet claims

The HV insulation grades list AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1, IEC 60840 and IEC 62067. The EHV insulation grades and both AC screens list AEIC CS9, ANSI/ICEA S-108-720 and IEC 62067. LE0550DC lists IEC 62895 and CIGRE TB 852. See IEC 60840 vs IEC 62067 for how the two IEC cable standards divide the voltage range.

Read the sentence above the list, if there is one. LS4201S, LE0592S and LE0500 say the grade is expected to meet the applicable requirements of the listed standards, provided it is processed using sound material handling and processing practices and appropriate testing procedures. LE4244S, LE4244EHV, LS4201EHV and LE0550DC print the list without that sentence. The sheets present it as a list of standards, not as a certificate.

Below the list, the AC sheets add a caveat: some standards may cover wider voltage ranges, but the statement applies up to the maximum recommended voltage level in the “Applications” section (LE0500 says “applies to” rather than “applies up to”). The LE0550DC sheet has no such caveat.

Physical properties: value, unit, method, footnote

Each row gives a property, a typical value, a unit and a test method. The asterisk on “Typical value” leads to “Data should not be used for specification work”. The small numbers are footnotes:

  • “Without peroxide” — on the insulation sheets, the melt flow rate (190 °C/2.16 kg) carries this footnote. LE4244S and LE4244EHV give 0.8 g/10 min; LS4201S and LS4201EHV give 2 g/10 min.
  • “Measured on crosslinked specimen(s)” — the tensile, ageing and hot-set rows. The insulation grades are tested at 250 mm/min, the semicons at 25 mm/min; keep the test speed in mind when comparing figures.
  • “Measured at time of production” — the moisture content row, e.g. < 200 ppm on LE4244S and LE0592S, < 100 ppm on LE0500.
  • “BTM = Borealis Test Method” — the methanol wash row on the insulation sheets: < 1000 ppm (LE4244 grades) and < 800 ppm (LS4201 grades), to BTM00118.

The rows also differ by family. Insulation sheets give base resin density (922 kg/m³), melt flow rate, MDR max torque as a range (3.1 – 4.5 dNm for LE4244, 2.9 – 3.8 dNm for LS4201) and methanol wash. Semicon sheets give “Density”, not base resin density (1135 kg/m³ for LE0592S, 1120 for LE0500, 1075 for LE0550DC), a single MDR max value (12, 14 and 11 dNm), and no melt flow rate or methanol wash. Ageing conditions differ too: most sheets use 135 °C for 168 h, while LE0592S uses 135 °C for 240 h.

A caution on LS4201S Ed.6: its physical table repeats the three electrical rows with broken symbols, a different dissipation factor (≤ 0.0005 against 0.0003) and IEC 62631 as the method, and its ageing row names IEC 60811-507 where the other sheets name IEC 60811-401. Use the Electrical properties table for the electrical values.

The test methods, and what each standard covers

Where a sheet cites a standard without a part number, the part named below is the one we checked on the official catalogue page, not one the sheet specifies.

Property on the sheet Test method cited What the standard covers (official catalogue page)
Base resin density / Density ISO 1183 ISO 1183-1:2025 — methods for the density of non-cellular plastics: void-free moulded or extruded objects, powders, flakes and granules
Melt flow rate (190 °C/2.16 kg) ISO 1133-1 MFR and MVR of thermoplastics under specified temperature and load; ISO notes the methods are used primarily in quality control
Tensile strain at break, tensile strength ISO 527 ISO 527-1:2019 — general principles for the tensile properties of plastics and plastic composites
Change of tensile properties after ageing IEC 60811-401 Ageing in an air oven, typically for crosslinked and thermoplastic insulating and sheathing compounds
Hot set (elongation under load, permanent deformation) IEC 60811-507 The hot set test, typically for cross-linkable insulating and sheathing compounds
MDR max torque / MDR max ISO 6502 ISO 6502-1:2025 — introduction to measuring vulcanization characteristics of rubber compounds with curemeters
Moisture content ISO 15512 Water content of plastics as powder, granules and finished articles, expressed as a mass fraction
Methanol wash BTM00118 A Borealis test method (the sheet’s footnote); no further detail given
DC volume resistivity (insulation) IEC 62631 IEC 62631-3-1:2023 — volume resistance and resistivity of insulating materials by applying a DC voltage
Dissipation factor, dielectric constant (50 Hz) IEC 60250 Permittivity and dissipation factor of insulating materials, about 15 Hz to 300 MHz; withdrawn 2018, replaced by IEC 62631-2-1:2018
DC volume resistivity (semicons) ISO 3915 Resistivity of conductive plastics below 10⁶ Ω·cm; ISO notes the result is not strictly a volume resistivity
DC volume resistivity (LE0500, 23 °C) ASTM D991 Volume resistivity of rubbers used in electrically conductive and antistatic products

Two points follow from the catalogue pages. IEC 60811-401 and IEC 60811-507 are both to be read with IEC 60811-100. And the IEC lists IEC 60250 as withdrawn in 2018 and replaced by IEC 62631-2-1. LE4244S, LS4201S and LE4244EHV still cite IEC 60250 for dissipation factor and dielectric constant; LS4201EHV Ed.3 cites IEC 62631 for those rows.

Electrical properties

The insulation sheets give DC volume resistivity at 23 °C of > 10 PΩ·cm (IEC 62631), a dissipation factor of 0.0003 and a dielectric constant of 2.3, both at 50 Hz. The AC semicon sheets give DC volume resistivity of < 100 Ω·cm at 23 °C and < 1000 Ω·cm at 90 °C (ISO 3915); LE0500 adds < 100 Ω·cm at 23 °C to ASTM D991, and LE0550DC gives the same two ISO 3915 figures. The 2026 PDFs drop the Ω glyph, so the unit prints as “P cm” or “cm” — read it as PΩ·cm or Ω·cm, as the 90 °C rows show.

Processing techniques

For the insulation grades the sheets call careful and very clean handling essential: all material handling should be conducted in closed systems and in clean room conditions (LE4244EHV says “should preferably”). A screen-pack on the extruder is recommended for improved melt homogenisation, and the typical melt temperature is 125 – 135 °C.

The semicon sheets add a drying setting. LE0592S and LE0500 give a melt temperature of 120 – 135 °C, LE0550DC 120 – 130 °C, and all three a drying temperature of 60 °C with footnote 3: 4 h with dehumidified air (the PDF text runs the footnote number into it as “34h”). Only LE0592S explicitly recommends drying before extrusion. See pre-drying.

Packaging and storage

This section names the package (Octabins for insulation, Smallbins for semicons) and the shelf life, which always runs from production date, in unopened original packages, under dry and clean conditions, within a temperature band. LE4244S and LE4244EHV: 12 months at 10 – 35 °C. LS4201S: 24 months at 5 – 35 °C. These three sheets also allow storage up to 40 °C for up to 6 months under the same conditions, and ask for the material to be conditioned indoors to ambient temperature before use. The semicons: 18 months at 10 – 30 °C. Every section recommends FIFO stock rotation and points to the SDS / PSIS for more storage information. LS4201EHV Ed.3 has no packaging and storage section. Our storage guide sets these side by side.

Product compliance documents

The latest PSIS, SDS and other product liability documents are on www.borealisgroup.com, separate from the data sheet.

The disclaimer

Three parts of the disclaimer shape how the sheet can be used:

  1. Typical values. The tables are marked as not for specification work, so the figures are not a specification.
  2. Testing is the customer’s job. The customer must inspect and test the products to satisfy itself that they suit its purpose, and is responsible for their safe and legal use, processing and handling.
  3. The product on its own. The information relates exclusively to the product when not used with any other material, except as provided for in the stated test methods, and Borealis accepts no liability for use with other products. The sheets do not recommend a particular screen and insulation combination.

The disclaimer also states that the products are not intended for medical, pharmaceutical or healthcare applications.

Supply from Shanghai

We supply all seven grades. Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and COA on request; we confirm availability of a given grade when you inquire. See our quality practice, the XLPE insulation and semiconductive screen overviews, and the insulation and screen grade comparisons. If a line on a sheet is unclear, ask us and we will send the current edition.