Borlink™ LS4201EHV
Supercure-based crosslinkable natural PE insulation for EHV AC cables.
Applications
Insulation of XLPE EHV AC cables rated above 230 kV (Um = 245 kV).
Key features
- Superclean insulation, assured by the Borealis quality system
- Very good electrical performance
- Excellent scorch resistance
- Reduced degassing burden — high productivity
Standards & specifications
As listed under “Specifications” on the producer’s data sheet, which notes that some standards may cover wider voltage ranges and limits its statement to the grade’s stated application.
Physical properties
| Property | Typical value | Test method |
|---|---|---|
| Density (base resin) | 922 kg/m³ | ISO 1183 |
| Melt flow rate (190 °C / 2.16 kg, without peroxide) | 2 g/10 min | ISO 1133-1 |
| Tensile strain at break (250 mm/min) | > 450 % | ISO 527 |
| Tensile strength (250 mm/min) | > 17 MPa | ISO 527 |
| Change of tensile props after ageing (135 °C, 168 h) | < 20 % | IEC 60811-401 |
| Hot set — elongation under load (200 °C, 0.20 MPa) | 75 % | IEC 60811-507 |
| Hot set — permanent deformation (200 °C, 0.20 MPa) | 5 % | IEC 60811-507 |
| MDR, max torque | 2.9 – 3.8 dNm | ISO 6502 |
| Methanol wash | < 800 ppm | BTM00118 |
| Moisture content (at production) | < 200 ppm | ISO 15512 |
Tensile, ageing and hot-set values are measured on crosslinked specimens.
Electrical properties
| Property | Typical value | Test method |
|---|---|---|
| Dielectric constant (50 Hz) | 2.3 | IEC 62631 |
| DC volume resistivity (23 °C) | > 10 PΩ·cm | IEC 62631 |
| Dissipation factor (50 Hz) | 0.0003 | IEC 62631 |
Typical values — for guidance, not for specification work.
Processing & storage
Buy Borlink™ LS4201EHV
We are an authorized distributor and hold core grades in our Shanghai warehouse — original sealed packaging, batch traceability and COA on request, exported worldwide. We confirm availability of a given grade when you inquire. See our quality practice, or read more about XLPE insulation compounds.
Further reading
- What is XLPE? Cross-linked polyethylene in power cables
- Borlink™ LE4244S vs LS4201S: XLPE grades compared
- How to read a Borlink™ data sheet
- HV cable materials glossary: XLPE, CCV, Um and more
- IEC 60840 vs IEC 62067 for HV cables: scope, Um, PQ test
- XLPE compound shelf life, storage and pre-drying
- Choosing XLPE insulation for 500 kV EHV cables
- Why superclean insulation matters at 220 kV and above