IEC 60840 vs IEC 62067 for HV cables: scope, Um, PQ test
Two IEC standards set the test methods and requirements for extruded-insulation power cables and their accessories in the transmission range. IEC 60840 covers rated voltages above 30 kV (Um = 36 kV) up to and including 150 kV (Um = 170 kV). IEC 62067 takes over above 150 kV (Um = 170 kV) and runs up to and including 500 kV (Um = 550 kV). Both are prepared by IEC technical committee 20, Electric cables.
This guide compares the current editions, using the IEC webstore listings, the free previews that standards sellers publish and the other sources listed at the end. It also shows which standards each Borlink™ grade we supply lists on its current data sheet. It is a reading aid, not a substitute for the standards themselves.
IEC 62067 in brief
- What it covers: power cable systems, cables with extruded insulation and their accessories for fixed installations, rated above 150 kV (Um = 170 kV) up to and including 500 kV (Um = 550 kV).
- Current edition: Ed.3.0, published 2022-04-21 by IEC technical committee 20. IEC 60840 Ed.5 covers the range below it, from above 30 kV up to 150 kV.
- Tests it sets: routine, sample and type tests, a prequalification test of the complete cable system, and electrical tests after installation.
- “IEC 62067 certified”: the standard qualifies cable systems, cables and accessories, not compounds. A type test or PQ certificate belongs to the cable system and its maker. A compound data sheet can only list the standard, in some sheets with a conditional “expected to meet” statement: see what a compound data sheet can claim.
Scope side by side
| IEC 60840 | IEC 62067 | |
|---|---|---|
| Current edition | Ed.5.0, published 2020-05-19. The consolidated Ed.5.1 (2023) incorporates Amendment 1:2023 and its 2025 corrigendum | Ed.3.0, published 2022-04-21. It cancels and replaces the second edition of 2011 |
| Rated voltages | Above 30 kV (Um = 36 kV) up to and including 150 kV (Um = 170 kV) | Above 150 kV (Um = 170 kV) up to and including 500 kV (Um = 550 kV) |
| Constructions | Single-core cables and individually screened three-core cables, with their accessories | Single-core cables and their accessories |
| Not covered | Special cables such as submarine cables; transition joints to paper-insulated cables | The same exclusions |
| Type approval | Of a cable system, of cables alone or of accessories alone (since the 2004 edition) | Type test defined for a type of cable system |
| Prequalification (PQ) | Since the 2011 edition, for cables with high electrical stresses | Since the first edition (2001) |
| Committee · stability date | IEC TC 20 · 2030 | IEC TC 20 · 2030 |
Which standard for which system voltage
Both standards are scoped by rated voltage and print the matching Um next to it. The table maps common nominal system voltages to a Um and to the standard whose scope covers them. Um is explained in the next section, and in our glossary.
| Nominal system voltage | Um | Cable test standard | Source for the Um |
|---|---|---|---|
| 110 kV / 115 kV | 123 kV | IEC 60840 | IEC 60038, Table 4 |
| 132 kV / 138 kV | 145 kV | IEC 60840 | IEC 60038, Table 4 |
| 150 kV (non-preferred in IEC 60038) | 170 kV | IEC 60840, its upper limit | IEC 60840 scope; IEC 60038, Table 4 |
| 220 kV / 230 kV | 245 kV | IEC 62067 | IEC 60038, Table 4 |
| 275 kV | 300 kV | IEC 62067 | ABB XLPE cable guide; IEC 60038 Table 5 lists 300 kV as non-preferred |
| 330 kV | 362 kV | IEC 62067 | ABB XLPE cable guide |
| 345 kV | Not given here | IEC 62067, by rated voltage | PJM uses 345 kV as a nominal voltage; we found no Um source |
| 380 kV | 420 kV | IEC 62067 | VDE FNN, Central European networks |
| 400 kV | 420 kV | IEC 62067 | IPTO TD-102/3 (Greece): Uo/U(Um) = 230/400(420) kV |
| 500 kV | 550 kV | IEC 62067, its upper limit | IEC 62067 scope |
Notes on the table:
- IEC 60038 Table 4 gives two series of nominal voltages side by side, for example 110 and 115 kV, 132 and 138 kV, 220 and 230 kV. It recommends that a country use only one series, and only one highest voltage for equipment from each group: 123 or 145 kV, and 245, 300 or 362 kV.
- Above 245 kV, IEC 60038 (Table 5) lists only highest voltages for equipment, not nominal system voltages. It includes 550 kV, the Um that IEC 62067 gives for 500 kV, with a note that 525 kV is also used.
- China’s cable standards print the Um in their titles: GB/T 11017.2-2024 for 66 kV (Um = 72.5 kV) and 110 kV (Um = 126 kV), in force since 2025-04-01; GB/T 18890.2-2015 for 220 kV (Um = 252 kV); and GB/T 22078.2-2008 for 500 kV (Um = 550 kV). These titles are from a reseller listing.
- The Borlink™ HV data sheets state their limit as rated 230 kV (Um = 245 kV). If a system’s Um is above 245 kV, as in the 220 kV (Um = 252 kV) designation above, or if no Um is stated, check with us.
- Above 500 kV (Um = 550 kV), neither standard’s scope applies.
What Um means
IEC 60183:2015 (Ed.3.0), the IEC guide to selecting high-voltage AC cable systems, designates cables U0/U (Um) to guide compatibility with switchgear and transformers (note to clause 3.1):
- U0: the rated voltage between each conductor and the screen or sheath.
- U: the rated voltage between any two conductors.
- Um, “highest system voltage” (3.1.3): the highest r.m.s. phase-to-phase voltage at power frequency that the cable system is designed for, under normal operation and not counting temporary variations caused by faults or by large loads being suddenly switched off.
Clause 5.3 says Um should be at least the highest voltage of the three-phase system. Greece’s transmission operator IPTO, for example, specifies its 400 kV XLPE cables as Uo/U(Um) = 230/400(420) kV.
IEC 60038, which sets the IEC standard voltages, does not use the symbol Um. Its term is “highest voltage for equipment” (3.9): the highest voltage for which equipment is specified regarding its insulation and related characteristics. Equipment may only be used on systems whose highest system voltage does not exceed it. The table above shows these values in its Um column. The current publication is IEC 60038:2009+AMD1:2021 (Ed.7.1), and the amendment’s listed changes leave the values used here as they are in the 2009 base text.
The Borlink™ AC data sheets also give their voltages as voltages between phases, as defined in IEC 60183.
Same test structure
The fourth edition of IEC 60840 (2011) coordinated its clause numbering with IEC 62067, and the current editions share the same sequence:
- Clause 9: routine tests on cables and accessories
- Clauses 10–11: sample tests on cables, then on accessories
- Clause 12: type tests on cable systems
- Clause 13: prequalification test of the cable system, with its extension in 13.3
- Clauses 14–15: type tests on cables, then on accessories
- Clause 16: electrical tests after installation
In IEC 62067, clauses 14 and 15 are short, and it defines its type test for a type of cable system (3.2.3).
In both standards, the manufacturer makes routine tests on each length of cable and each accessory, and sample tests on samples taken at a specified frequency. Type tests are made before a type is supplied on a general commercial basis. In IEC 60840 the type can be a cable system, a cable or an accessory; in IEC 62067 it is a cable system. Type tests need not be repeated unless the materials, design or manufacturing process change in a way that might change the performance characteristics.
Prequalification
IEC 62067. On CIGRE’s advice, the first edition introduced a long-term accelerated ageing test on the complete system of cable, joints and terminations, known as the prequalification test. The 2022 edition defines it as a test made before a type of cable system is supplied on a general commercial basis, to demonstrate satisfactory long-term performance of the complete system. Following CIGRE Technical Brochure 303, the second edition (2011) added an extension of prequalification (EQ) test, which takes an already prequalified system into account. According to the introduction, it takes about one quarter of the time of a full PQ test.
IEC 60840. PQ arrived with the fourth edition (2011), for cable designs with high electrical stress at the conductor screen, the insulation screen or both. Clause 13.1, as replaced by Amendment 1:2023, sets three rules:
- When it is required: where the calculated nominal electrical stress is above 8.0 kV/mm at the conductor screen and/or above 4.0 kV/mm at the insulation screen.
- The three exceptions: a cable system of the same construction, with accessories of the same family, is already prequalified at an equal or higher rated voltage; or the manufacturer can show good service experience with systems at equal or higher calculated stresses at the conductor and insulation screens, including in the accessories; or it has passed an equivalent long-term test, under a national or customer specification, on a cable system of the same construction with accessories of the same family, at an equal or higher voltage rating.
- What a pass covers: cable systems of the same family at the same or lower voltage ratings, provided the calculated stress at the insulation screen is no higher than in the tested system.
Nominal electrical stress is calculated at U0 using nominal dimensions and is expressed in kV/mm; IEC 62067 gives the equations in Clause 6, item n). See also the prequalification test entry in our glossary.
What the test involved (2011 edition). KEMA Laboratories described the PQ test of the second (2011) edition of IEC 62067 as about 100 m of complete cable with at least one of each type of accessory. The loop is installed under various laying conditions, such as direct buried, rigidly in a tunnel or in a duct. It runs a one-year (8 760 h) heating cycle voltage test with at least 180 cycles of at least 24 h each, followed by a lightning impulse voltage test and an examination. We have not compared this with the 2022 text, so check the current edition for today’s requirements.
In utility specifications. IPTO’s 400 kV cable specification (TD-102/3, March 2017) makes a PQ certificate to clause 13 of IEC 62067 a prerequisite. It must cover cable systems of at least 400 kV rated voltage (420 kV maximum) and 1 550 kV lightning impulse withstand. A cable whose manufacturer lacks it will not be accepted.
Why above 150 kV is treated separately
The introduction to IEC 62067 records four reasons, from CIGRE Working Group 21.03, why voltages above 150 kV need extra consideration:
- These cables form part of the backbone of the transmission system, so reliability has the highest priority.
- They and their accessories run at higher electrical stresses than cables up to 150 kV, with a smaller safety margin to the system’s intrinsic performance limits.
- Their thicker insulation walls bring greater thermo-mechanical effects.
- Designing and coordinating cables and accessories gets harder as the system voltage rises.
Tests after installation
IEC 62067 defines an electrical test after installation as one that demonstrates the integrity of the cable system as installed. Clause 16 of both standards covers these on-site tests: a DC voltage test of the oversheath, and tests using AC voltage. In IEC 62067:2022 the AC tests are an AC voltage test of the insulation (16.3.1) and a partial discharge test (16.3.2). The 2011 edition’s clause 16 listed no partial discharge test, and the 2022 foreword says AC testing after installation was revised in line with recent CIGRE recommendations.
The introduction to IEC 62067 also records the advice of CIGRE WG 21.09 (Electra 173, 1997) to avoid DC tests on the main insulation, because such tests are ineffective and can cause damage.
What changed in the current editions
The current editions are IEC 60840 Ed.5 (2020, with Amendment 1 of 2023) and IEC 62067 Ed.3 (2022). The main changes in their forewords concern oversheaths (the ST12 class and fire tests), conductor water penetration, bending tests, terminations and, in IEC 62067, AC testing after installation.
What a compound data sheet can claim
Neither scope lists insulation or screen compounds among the things it covers: the objects are cable systems, cables and accessories. The cable or accessory manufacturer makes the routine and sample tests, and a passed PQ test qualifies the manufacturer as a supplier of cable systems.
The Borlink™ data sheets list their standards under “Specifications”. In their Specifications section, table footnotes and disclaimer, the six AC sheets say:
- Expected to meet. The LS4201S, LE0592S and LE0500 sheets say the grade “is expected to meet the applicable requirements” of the listed standards. The condition is that it is processed using sound material handling and processing practices, with appropriate testing procedures. The LE4244S, LE4244EHV and LS4201EHV sheets give the list without this sentence.
- Voltage scope. All six add that some standards may cover wider voltage ranges, and that the statement applies up to the maximum recommended voltage stated in the sheet’s application text (the sheets call it the “Applications” section; on most 2026 sheets it is part of the Description). For the HV grades, that is cables rated up to 230 kV (Um = 245 kV). The EHV sheets state their application as AC cables rated above 230 kV and give no upper figure.
- Typical values. In Borealis’s words, the property figures “should not be used for specification work”.
- Suitability. Testing a product’s suitability for the customer’s purpose is the customer’s responsibility. The information relates only to each product when it is not used with other materials.
So a standard on a compound’s list is the producer’s statement, made with these conditions. It is not a type test or PQ certificate for anyone’s cable. Our quality page lists the standards and test methods named on the current sheets.
Which Borlink™ grades list which standard
| Grade and data sheet | Stated application | Standards listed |
|---|---|---|
| LE4244S insulation · Ed.4, 2026 | HV AC cables rated up to 230 kV (Um = 245 kV) | IEC 60840, IEC 62067, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1 |
| LS4201S insulation · Ed.6, 2026 | HV AC cables rated up to 230 kV (Um = 245 kV) | IEC 60840, IEC 62067, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1 |
| LE0592S semiconductive · Ed.5, 2026 | Conductor screen, and insulation screen in bonded constructions, of HV AC cables rated up to 230 kV (Um = 245 kV) | IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 |
| LE4244EHV insulation · Ed.4, 2026 | EHV AC cables rated above 230 kV | IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 |
| LS4201EHV insulation · Ed.3, 2026 | EHV AC cables rated above 230 kV | IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 |
| LE0500 semiconductive · Ed.4, 2026 | Conductor screen and bonded insulation screen of EHV AC cables rated above 230 kV | IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 |
| LE0550DC semiconductive · Ed.1, 2026 | Semiconductive screens of XLPE HVDC cables; no voltage rating given | IEC 62895, CIGRE TB 852 |
Three points stand out:
- Two different lines. The test standards split at 150 kV, while the grade bands split at 230 kV. So a 220 or 230 kV cable with Um = 245 kV is tested to IEC 62067 but falls within the stated application of the HV grades (rated up to 230 kV, Um = 245 kV). Where the Um is higher, such as 252 kV, see the note above. Our 220 kV page covers this boundary case, and our XLPE insulation page lists all four insulation grades.
- LE0592S. Although it is an HV grade, its current sheet lists IEC 62067 but not IEC 60840 among the IEC cable standards. We print the list as the sheet gives it. If your cable specification names a standard that is not on a grade’s list, contact us for project-specific standards and the current data sheet; qualifying the cable to that standard remains the cable maker’s task.
- LE0550DC. The HVDC screen grade we supply lists neither standard discussed here. It lists IEC 62895, the IEC standard (current edition 2017) for HVDC cables with extruded insulation rated up to 320 kV for land applications, and CIGRE TB 852 (2021), recommendations for testing DC extruded cable systems rated up to and including 800 kV.
North American and European counterparts
All six AC sheets also list AEIC CS9 and ANSI/ICEA S-108-720. AEIC presents itself as a non-competitive forum for North American utility operators to compare practice, with more than 190 member utilities across the US and Canada. ICEA, the Insulated Cable Engineers Association, develops cable standards and notes that many of them are approved by the American National Standards Institute (ANSI). ABB’s XLPE Land Cable Systems User’s Guide (rev 5, 2010) notes that North American cables are often specified according to ICEA. We could not confirm the current scope of CS9 or S-108-720 from an official source, so we give no voltage ranges for them.
The two HV insulation sheets also list HD 632 S1. ABB’s 2010 guide lists HD 632 among the CENELEC documents, for extruded cables up to 150 kV (Um = 170 kV), and says its Part 1 is based on IEC 60840 and follows it closely. It adds that CENELEC cable standards are, as a rule, implementations of the IEC specifications.
Supply from Shanghai
We supply all six AC grades. Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and a COA on request; we confirm availability of a given grade when you inquire. Tell us your system voltage, the Um and the standard your cable will be tested to. We will confirm which grades have a stated application that covers it, and send the current data sheets.
References
- PDF · Borlink™ LE4244S product data sheet · Borealis, Ed.4, 6 Mar 2026
- PDF · Borlink™ LS4201S product data sheet · Borealis, Ed.6, 5 May 2026
- PDF · Borlink™ LE0592S product data sheet · Borealis, Ed.5, 6 Mar 2026
- PDF · Borlink™ LE4244EHV product data sheet · Borealis, Ed.4, 6 Mar 2026
- PDF · Borlink™ LS4201EHV product data sheet · Borealis, Ed.3, 5 May 2026
- PDF · Borlink™ LE0500 product data sheet · Borealis, Ed.4, 6 Mar 2026
- PDF · Borlink™ LE0550DC product data sheet · Borealis, Ed.1, 7 Apr 2026
- STANDARD · IEC 60840:2020 (IEC webstore) · Ed.5.0, 2020-05-19; scope, TC 20, stability date 2030
- STANDARD · IEC 60840:2020/AMD1:2023 (IEC webstore) · Amendment 1, 2023-06-02; corrected version 2025-06
- PREVIEW · IEC 60840 Ed.5.1 preview (VDE Verlag) · Foreword, introduction, contents and scope of the consolidated text
- PREVIEW · IEC 60840:2020/AMD1:2023 preview (SIST) · Replacement text of clause 13.1
- PREVIEW · IEC 60840:2020 sample (iTeh) · Definitions 3.2.1–3.2.3
- STANDARD · IEC 62067:2022 (IEC webstore) · Ed.3.0, 2022-04-21; scope, TC 20, stability date 2030
- PREVIEW · IEC 62067 Ed.3.0 preview (VDE Verlag) · Foreword, introduction and contents
- PREVIEW · IEC 62067:2022 sample (iTeh) · Definitions 3.2.1–3.2.6 and 3.3.2
- PREVIEW · IEC 62067 Ed.2.0 (2011) preview (VDE Verlag) · 2011 contents of clause 16; first edition 2001
- STANDARD · IEC 60038:2009+AMD1:2021 (IEC webstore) · Ed.7.1, 2021-12-15; list of the amendment’s changes
- STANDARD · IEC 60038:2009 base text · 3.9, Tables 4 and 5 with their notes
- PREVIEW · IEC 60183:2015 sample (iTeh) · Ed.3.0; 3.1 note, 3.1.1–3.1.3 and 5.3
- STANDARD · IEC 62895:2017 (IEC webstore) · HVDC cables with extruded insulation up to 320 kV, land applications
- BROCHURE · CIGRE TB 852 · WG B1.62, 2021; DC extruded cable systems up to and including 800 kV
- PAPER · How to perform a prequalification test (KEMA Laboratories, Jicable’15 D6.2) · Describes the PQ test of the 2011 edition of IEC 62067
- SPEC · IPTO TD-102/3: single-core underground 400 kV XLPE cables · March 2017; 230/400(420) kV; PQ certificate as a prerequisite
- STUDY · VDE FNN study on voltages above Um (summary) · 380 kV networks in Central Europe, rated 420 kV
- SPEC · PJM design criteria for electrical facilities · 345 kV as a nominal transmission voltage
- LISTING · GB/T 11017.2-2024 (chinesestandard.net) · Reseller listing; 66 kV (Um = 72.5 kV) and 110 kV (Um = 126 kV); in force 2025-04-01
- LISTING · GB/T 18890.2-2015 (chinesestandard.net) · Reseller listing; 220 kV (Um = 252 kV)
- LISTING · GB/T 22078.2-2008 (chinesestandard.net) · Reseller listing; 500 kV (Um = 550 kV)
- ORG · AEIC · North American utility forum, 190+ member utilities
- ORG · ICEA · Cable standards body; many standards ANSI-approved
- GUIDE · ABB XLPE Submarine Cable Systems, attachment to the XLPE Land Cable Systems User’s Guide (rev 5) · Gives 275 kV (Um = 300 kV) and 330 kV (Um = 362 kV), as does the land guide (2GM 5007 GB rev 5, 2010-04), which is our source for the ICEA and HD 632 notes; we found no official online copy of the land guide
Related products
- Borlink™ LE4244S · Insulation
- Borlink™ LS4201S · Insulation
- Borlink™ LE0592S · Semiconductive
- Borlink™ LE4244EHV · Insulation
- Borlink™ LS4201EHV · Insulation
- Borlink™ LE0500 · Semiconductive