Voltage class · EHV

330 kV / 345 kV cable insulation & semiconductive compounds

For 330 kV, North America’s 345 kV and the 275 kV class below them, the Borlink™ grades are LE4244EHV or LS4201EHV insulation and the LE0500 screen; the cable maker selects and qualifies the pair. All are rated above 230 kV, where the Borealis data sheets move to the Borlink™ EHV grades, and IEC 62067 is the cable test standard. Check your Um, any North American specification and your insulation wall, then send us your cable design, grade and volume. We supply all three grades; core grades are held in our Shanghai warehouse.

Grades for 330 kV cables

LayerGradeNotes
XLPE insulation Borlink™ LE4244EHV Very low sagging — horizontal lines and thick CCV walls
XLPE insulation Borlink™ LS4201EHV Excellent scorch resistance; reduced degassing burden
Conductor & bonded insulation screen Borlink™ LE0500 Supersmooth screen; robust extrusion at high surface temperature

Choosing between the insulation grades: LE4244EHV has very low sagging properties and is specially designed for extrusion on horizontal lines and for thick insulation walls on CCV lines. LS4201EHV is based on Supercure technology, and its sheet separately lists very good electrical performance, excellent scorch resistance for long production runs and high productivity from a reduced degassing burden. Horizontal lines or thick CCV walls point to LE4244EHV; long runs or a lighter degassing burden point to LS4201EHV. Compare them in LE4244EHV vs LS4201EHV.

All four insulation sheets state superclean insulation, assured through the Borealis Quality Management system. More on XLPE insulation and semiconductive screens.

330 kV at a glance

Rated voltage U (phase to phase)330 kV (345 kV in North America and Korea)
Highest system voltage Um362 kV (ABB guide, Table 30; one of the IEC 60038 Table 5 values)
Cable test standardIEC 62067, whose range runs from above 150 kV to 500 kV (Um = 550 kV)
Constructions coveredSingle-core cables; submarine cables excluded
Borlink™ bandEHV AC: rated above 230 kV
Grades we supply LE4244EHV, LS4201EHV, LE0500

Which standard applies

IEC 62067 applies to this class. Its range takes in 275, 330 and 345 kV.

For North American projects, check your specification against AEIC CS9 and ANSI/ICEA S-108-720, both North American documents. ABB’s 2010 guide notes that North American cables are often specified to ICEA standards and gives S-108-720’s range as above 46 through 345 kV.

Every data sheet on this page lists IEC 62067, AEIC CS9 and ANSI/ICEA S-108-720 under “Specifications”.

The LE0500 sheet says the grade “is expected to meet the applicable requirements” of the listed standards, provided it is processed using sound material handling and processing practices and appropriate testing procedures; the LE4244EHV and LS4201EHV sheets list their standards without that sentence. The EHV sheets apply these listings only up to the sheet’s recommended maximum voltage, although some standards may cover wider voltage ranges; they give no upper voltage figure. See also our quality & standards page.

What to check

System voltage and Um

Nominal voltageUmBasis
275 kV300 kVNon-preferred in IEC 60038; ABB guide, Table 29; National Grid TS1 (rated voltage of plant)
330 kV362 kVABB guide, Table 30; 362 kV is an IEC 60038 Table 5 value
345 kV—PJM operating range 325–362 kV

Systems in this class include 330 kV in China’s Northwest Power Network and Transgrid’s NSW network, 275 or 330 kV connections for projects above 150 MW in Queensland (Powerlink), and Great Britain’s 275 kV lines.

Above 245 kV, IEC 60038 lists only highest voltages for equipment, not nominal voltages, and recommends one of 245, 300 or 362 kV per country. All three rows are rated above 230 kV, the EHV sheets’ stated application; those sheets give no upper figure.

Design and testing

  • Test cable and joints as a system. ISO New England’s 2005 review of 345 kV underground cable treated it as extra-high voltage, noted that there were then few XLPE cable systems above 300 kV, and recommended two cables per phase and testing cable and splices as a system.
  • Insulation wall. ABB’s land cable guide (rev. 5, 2010) lists single-core 330 kV cables with 28.0 mm of insulation at 630 mm² and 25.0 mm from 1200 to 2500 mm², and 275 kV cables with 26.0 mm at 500 mm² and 24.0 mm from 630 mm². These are indicative, non-binding data, and walls differ at the same voltage: VISCAS reports 23 mm (Tokyo, Kansai) and 27 mm (Chubu) of insulation on Japanese 275 kV XLPE cables. Size the wall from your own design.
  • Your own testing. Each sheet describes its grade used alone and leaves suitability testing to the customer.

How to inquire

Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and COA on request: short lead times, no waiting for a production run. We confirm availability of a given grade when you inquire. What each data sheet says on shelf life and storage is in our storage guide.

Tell us your cable design, grade and volume, and we reply with availability, data sheets and pricing. Request a quote →

345 kV XLPE cable examples

  • K Street, Boston (2006): Brugg Cables’ first 345 kV XLPE underground installation in the US, two 600 MVA circuits.
  • KEPCO and LS Cable & System developed a 345 kV, 2,500 mm² optical-fibre composite XLPE cable to replace large-capacity overhead lines.

Shown to illustrate the voltage class, not projects supplied by Lexin.

Further reading

Building an HVDC link? Borlink™ LE0550DC is a semiconductive compound for XLPE HVDC cable screens; its data sheet lists IEC 62895 and CIGRE TB 852 and states no voltage rating.

References

Other voltage classes

110 kV · 220 kV · 500 kV · All products