Borlink™ LE4244S vs LS4201S: XLPE grades compared
We supply four Borlink™ XLPE insulation grades from Borealis. They come in two families, LE4244 and LS4201, and each family has an HV and an EHV version. LE4244S and LS4201S are intended for HV AC cables rated up to 230 kV (Um = 245 kV). LE4244EHV and LS4201EHV are intended for EHV AC cables rated above 230 kV.
Every grade fact below comes from the producer’s current data sheets (the 2026 editions, linked in the table). Background on terms such as sagging, scorch and degassing, and the IEC scopes, comes from the sources listed under References. The property figures are typical values, and Borealis says they should not be used for specification work. The sheets also make it the customer’s responsibility to test the material for its own purpose.
At a glance
| Data sheet item | LE4244S | LS4201S | LE4244EHV | LS4201EHV |
|---|---|---|---|---|
| Application | HV AC, rated up to 230 kV (Um = 245 kV) | HV AC, rated up to 230 kV (Um = 245 kV) | EHV AC, rated above 230 kV | EHV AC, rated above 230 kV |
| Supercure technology | Not mentioned | Based on Supercure technology | Not mentioned | Based on Supercure technology |
| Feature text (Description) | Very low sagging; for horizontal lines and thick insulation walls on CCV lines | Very good electrical performance; excellent scorch resistance for long production runs; reduced degassing burden for high productivity | Very low sagging; for horizontal lines and thick insulation walls on CCV lines | Very good electrical performance; excellent scorch resistance for long production runs; reduced degassing burden for high productivity |
| Superclean insulation stated | Yes | Yes | Yes | Yes |
| Melt flow rate (190 °C / 2.16 kg, without peroxide) | 0.8 g/10 min | 2 g/10 min | 0.8 g/10 min | 2 g/10 min |
| MDR, max torque | 3.1 – 4.5 dNm | 2.9 – 3.8 dNm | 3.1 – 4.5 dNm | 2.9 – 3.8 dNm |
| Methanol wash (BTM00118) | < 1000 ppm | < 800 ppm | < 1000 ppm | < 800 ppm |
| Standards listed | 5: IEC 60840, IEC 62067, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1 | 5: as LE4244S | 3: IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 | 3: as LE4244EHV |
| Shelf life | 12 months | 24 months | 12 months | Not stated on Ed.3 |
| Storage window | 10 – 35 °C | 5 – 35 °C | 10 – 35 °C | Not stated on Ed.3 |
| Data sheet | Ed.4, 6 Mar 2026 | Ed.6, 5 May 2026 | Ed.4, 6 Mar 2026 | Ed.3, 5 May 2026 |
In short, the sheets give each family its own focus. LE4244 is the low-sagging family, designed for horizontal lines and for thick insulation walls on CCV lines. LS4201 is based on Supercure technology; its sheets also list very good electrical performance, excellent scorch resistance and a reduced degassing burden. Which focus suits your line and process is for you to decide and test. The sections below go through each point.
LE4244: very low sagging for horizontal and CCV lines
Both LE4244 sheets say the grade has very low sagging properties. They also say it is specially designed for extrusion on horizontal lines and for cables with thick insulation walls extruded on CCV lines. The sheets do not say how the low sagging is achieved. We do not read it into the melt flow rate or any other figure in the table.
What sagging means: a Borealis patent on a polyethylene composition for cables (US 11,708,431 B2) describes the problem in general terms. While the insulation is still molten, the conductor can sink within it, or soft insulation can drop off the conductor. Either way the insulation moves downward and the core becomes eccentric; the patent’s example is a pear-shaped core. It adds that better sagging resistance is needed for big cable constructions and for production on catenary and horizontal lines. The patent names no Borlink grade. We cite it only to explain the term.
Line builder Maillefer describes the same effect on catenary (CCV) lines: when the melt near the conductor loses viscosity, for example through rapid heating, “significant drooping occurs and the insulation will be off-centered”. Maillefer names no compound; its page presents its own line process as the remedy. The LE4244 sheets name the conditions the grades are designed for: horizontal lines, and thick insulation walls on CCV lines.
LS4201: Supercure, scorch resistance and a reduced degassing burden
Both LS4201 sheets describe the compound as based on Supercure technology. In a separate passage they say the grade:
- provides very good electrical performance
- offers excellent scorch resistance enabling long production runs
- is specially designed for high productivity due to a reduced degassing burden
The sheets do not describe Supercure, and they do not say which of these properties come from it.
Scorch. A Borealis patent on scorch-resistant polyethylene compositions (EP 2 468 813 A1, published 2012) explains the term. If a significant amount of peroxide already breaks down in the extruder, cross-linking starts too early. The result is so-called scorch: inhomogeneity, surface unevenness and possibly discoloration in the cable layers. The patent names neither Borlink nor Supercure; we cite it only for the definition. The LS4201 sheets link their scorch resistance to long production runs, and neither gives a scorch-time figure.
Degassing. A Jicable’11 paper by authors from Ericsson and Borealis (Andersson et al., E.7.1.3) explains why HV XLPE cable cores are degassed, for both technical and safety reasons:
- Peroxide cross-linking releases methane. It must be removed to eliminate the risk of fire or explosion during handling and installation.
- The polar by-products, mainly acetophenone and cumyl alcohol, influence electrical properties such as dissipation factor and space charge accumulation.
The paper describes its test insulation only as a compound developed for a lower degassing burden and does not name it, so we do not treat it as describing LS4201. The LS4201 sheets state the design aim, high productivity due to a reduced degassing burden. They give no degassing times or by-product figures.
What the four grades share
Typical values, not for specification work. All four 2026 sheets print the same figures for these properties:
- Base resin density: 922 kg/m³ (ISO 1183)
- Tensile strain at break > 450 % and tensile strength > 17 MPa, at 250 mm/min on crosslinked specimens (ISO 527)
- Change of tensile properties after ageing at 135 °C for 168 h: < 20 %
- Hot set (200 °C, 0.20 MPa): elongation under load 75 %, permanent deformation 5 % (IEC 60811-507)
- Moisture content < 200 ppm, measured at the time of production (ISO 15512)
- Dielectric constant 2.3 and dissipation factor 0.0003, both at 50 Hz; DC volume resistivity (23 °C) > 10 PΩ·cm
- Melt temperature 125 – 135 °C
All four also recommend a screen-pack on the extruder for improved melt homogenisation.
One quirk: the LS4201S sheet (Ed.6) repeats three electrical rows in its physical-property table, two with different figures (dissipation factor ≤ 0.0005, and resistivity printed as ≥ 10 “Ohmcm”). We quote the values from its Electrical properties table.
The four sheets also share the same cleanliness text. Each sheet says the grade’s cleanliness and consistency give superclean cable insulation, assured through Borealis’s quality management system and checked at several process steps with Borealis’s own analysis methods. All four call for careful, very clean handling, with material handling in closed systems and clean-room conditions. The LE4244EHV sheet says this “should preferably be conducted”; the other three say “should be conducted”. For more on why this matters, see why superclean insulation matters and our XLPE insulation page.
HV or EHV version?
The data sheets state each grade’s intended HV or EHV application by rated voltage and Um:
- HV versions: AC cables rated up to 230 kV (Um = 245 kV)
- EHV versions: AC cables rated above 230 kV
The EHV sheets print “(Um = 245 kV)” after “above 230 kV”; that is the Um of the 230 kV boundary, not of an EHV cable. The values are voltages between phases as defined in IEC 60183. If a system is rated 230 kV or below but its Um is above 245 kV, or its Um is not stated, check with us before you choose a version.
In the current editions, the three main differences between the HV and EHV versions of each family are:
- Application. The voltage band above.
- Standards listed. The HV sheets list five: IEC 60840, IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 and HD 632 S1. The EHV sheets list three: IEC 62067, AEIC CS9 and ANSI/ICEA S-108-720. Each sheet adds that some standards may cover wider voltage ranges, and ties its listing to the application it states.
- Storage data (LS4201 family). LS4201S states 24 months at 5 – 35 °C; the LS4201EHV sheet has no packaging and storage section.
Within each family, the HV and EHV sheets print the same feature text, the same typical values (apart from the LS4201S duplicate rows noted above) and the same melt temperature. Both families state superclean insulation in both versions.
Other wording differences in the current editions:
- Of the four insulation sheets, only LS4201S says the grade is expected to meet the applicable requirements of the listed standards. Its condition is that the grade is processed using sound material handling and processing practices, with appropriate testing procedures. The other three sheets list the same kind of standards without that sentence.
- LE4244EHV’s handling sentence adds preferably, as noted above.
The IEC cable-system test standards draw their line elsewhere. IEC 60840 covers rated voltages above 30 kV up to and including 150 kV (Um = 170 kV). IEC 62067 covers above 150 kV up to and including 500 kV (Um = 550 kV). So the standards split at 150 kV, while the grades split at 230 kV. A 220 or 230 kV cable with Um = 245 kV falls within the voltage range of IEC 62067 and within the stated application of the HV grades; for a higher or unstated Um, see the check above. See IEC 60840 vs IEC 62067 for the detail, and our 220 kV and 330 kV pages, one on each side of the 230 kV line.
Screens for the same voltage bands
The same 230 kV line runs through the semiconductive screen grades:
- LE0592S is intended for semiconductive screens of XLPE HV AC cables rated up to 230 kV (Um = 245 kV). It can be used as the conductor and insulation screen in bonded constructions, and as the conductor screen in strippable ones (see bonded and strippable screens).
- LE0500 is a supersmooth compound for the conductor screen and bonded insulation screen of EHV AC cables rated above 230 kV.
No data sheet recommends combining a particular screen with a particular insulation grade. Each sheet says its information relates only to that product when not used with other materials, and Borealis accepts no liability for use in conjunction with other products. Each also leaves the customer to test suitability for the intended purpose. Choosing and qualifying a screen and insulation combination is the cable maker’s job. For the role of each layer, see semiconductive screens vs. insulation.
Shelf life and storage
Three of the four sheets give the same storage text. Only the shelf life and the storage window differ:
- LE4244S and LE4244EHV: 12 months from production date, in unopened original packages under dry and clean conditions, at 10 – 35 °C (50 – 95 °F).
- LS4201S: 24 months under the same conditions, at 5 – 35 °C (41 – 95 °F).
These three sheets also say:
- Material in unopened original packages, kept dry and clean, can be stored at ambient temperature up to 40 °C (104 °F) for up to 6 months.
- Storage conditions affect shelf life, and extreme conditions affect material quality and performance.
- Before use, material is to be conditioned indoors to reach ambient temperature.
- They recommend first in, first out stock rotation and refer to the SDS / PSIS for more on storage.
The LS4201EHV sheet (Ed.3) has no packaging and storage section, so we give no shelf life for it. Its product compliance section points to the latest safety documents on borealisgroup.com. Ask us before you plan long storage of LS4201EHV. Our storage guide covers shelf life for every Borlink grade we supply.
Supply from Shanghai
We supply all four grades. Core grades are held in our Shanghai warehouse in original sealed packaging, unopened until dispatch; we confirm availability of a given grade when you inquire. Stock is stored dry and clean, with FIFO rotation. Every lot is traceable to its production batch, and a COA is available on request. Tell us your voltage class, line type and volume, and we will confirm availability and send the current data sheets.
References
- PDF · Borlink™ LE4244S product data sheet · Borealis, Ed.4, 6 Mar 2026
- PDF · Borlink™ LS4201S product data sheet · Borealis, Ed.6, 5 May 2026
- PDF · Borlink™ LE4244EHV product data sheet · Borealis, Ed.4, 6 Mar 2026
- PDF · Borlink™ LS4201EHV product data sheet · Borealis, Ed.3, 5 May 2026
- PDF · Borlink™ LE0592S product data sheet · Borealis, Ed.5, 6 Mar 2026
- PDF · Borlink™ LE0500 product data sheet · Borealis, Ed.4, 6 Mar 2026
- STANDARD · IEC 60840:2020 (Ed.5.0; consolidated with AMD1:2023), IEC webstore · Scope above 30 kV up to 150 kV (Um = 170 kV)
- STANDARD · IEC 62067:2022 (IEC webstore) · Scope above 150 kV up to 500 kV (Um = 550 kV)
- PATENT · EP 2 468 813 A1, Scorch resistant polyethylene composition · Borealis GmbH, 2012; explains scorch, names no Borlink grade
- PATENT · US 11,708,431 B2, Polymer composition comprising a polyethylene · Borealis GmbH, priority 2017; explains sagging, names no Borlink grade
- PAPER · Distribution of peroxide by-products along degassed XLPE HV cables · Andersson (Ericsson AB), Jakobsson, Smedberg, Boström (Borealis AB), Jicable’11, E.7.1.3
- BRAND · Maillefer: high voltage catenary continuous vulcanizing · CCV line builder; drooping on catenary lines
Related products
- Borlink™ LE4244S · Insulation
- Borlink™ LS4201S · Insulation
- Borlink™ LE4244EHV · Insulation
- Borlink™ LS4201EHV · Insulation
See also
- How to read a Borlink™ data sheet
- LE0592S vs LE0500: Borlink™ semicon screens compared
- IEC 60840 vs IEC 62067: scope, Um, prequalification
- XLPE compound shelf life, storage and pre-drying
- HV cable materials glossary: XLPE, CCV, Um and more
- Choosing XLPE insulation for 500 kV EHV cables
- Why superclean insulation matters at 220 kV and above