LE0592S vs LE0500: Borlink™ semicon screens compared

· Selection

Sealed smallbins of cable compound on pallets in a warehouse aisle (illustration)

We supply two Borlink™ semiconductive screen compounds for AC power cables. LE0592S is intended for HV AC cables rated up to 230 kV (Um = 245 kV). LE0500 is intended for EHV AC cables rated above 230 kV. A third grade, LE0550DC, is for HVDC cables and is covered briefly at the end.

Every grade fact below comes from the producer’s 2026 data sheets (linked in the table and under References). The property figures are typical values, and Borealis says they should not be used for specification work. The sheets also make it the customer’s responsibility to test the material for its own purpose. For what the screen layers do, see semiconductive screens vs. insulation.

At a glance

Data sheet item LE0592S LE0500
Application HV AC, rated up to 230 kV (Um = 245 kV) EHV AC, rated above 230 kV
Screen roles stated Conductor screen and bonded insulation screen; also the conductor screen in strippable constructions Conductor screen and bonded insulation screen
Smoothness wording “very smooth” screen “supersmooth” compound; “superior smoothness”
Density 1135 kg/m³ 1120 kg/m³
MDR max 12 dNm 14 dNm
Moisture content (at production) < 200 ppm < 100 ppm
Ageing (change of tensile properties) < 25 % after 135 °C, 240 h < 20 % after 135 °C, 168 h
DC volume resistivity < 100 Ω·cm (23 °C), < 1000 Ω·cm (90 °C) < 100 Ω·cm (23 °C), < 1000 Ω·cm (90 °C); also < 100 Ω·cm at 23 °C to ASTM D991
Standards listed IEC 62067, AEIC CS9, ANSI/ICEA S-108-720 IEC 62067, AEIC CS9, ANSI/ICEA S-108-720
Melt temperature 120 – 135 °C 120 – 135 °C
Drying (typical) 60 °C, 4 h, dehumidified air 60 °C, 4 h, dehumidified air
Package · shelf life · storage Smallbins · 18 months · 10 – 30 °C Smallbins · 18 months · 10 – 30 °C
Data sheet Ed.5, 6 Mar 2026 Ed.4, 6 Mar 2026

In short: the two grades follow the same voltage line as the insulation grades we supply. LE0592S is the HV screen and LE0500 the EHV screen. Their standards lists, melt temperature, drying setting, packaging and storage terms are the same; their application, screen roles, smoothness wording and several typical values differ.

Application: HV or EHV

The sheets state each grade’s intended application by rated voltage and Um. LE0592S is intended for XLPE HV AC cables rated up to 230 kV (Um = 245 kV); LE0500 for XLPE EHV AC cables rated above 230 kV. The EHV sheet also prints “(Um = 245 kV)” after “above 230 kV” — the same Um the HV sheet gives for its 230 kV upper limit; the EHV sheet states no Um of its own for EHV cables. Both sheets give the values as voltages between phases as defined in IEC 60183.

A rated voltage of 110 kV or 220 kV falls within LE0592S’s stated range (up to 230 kV, Um = 245 kV); 330 kV or 500 kV falls within LE0500’s (above 230 kV). If your system’s Um is above 245 kV at a rated voltage of 230 kV or below, or you are unsure, check with us.

Which screen layers each grade is for

Where the semiconductive screens sit in an extruded HV or EHV cable coreSchematic cross-section, not to scale. From the centre: conductor; semiconductive conductor screen; XLPE insulation; semiconductive insulation screen; then the metallic screen and sheath. Both screen layers are where LE0592S (HV) or LE0500 (EHV) are used, the insulation screen in bonded constructions.Conductorcopper or aluminiumConductor screen — semiconductiveLE0592S (HV) · LE0500 (EHV)InsulationXLPEInsulation screen — semiconductive, bondedLE0592S (HV) · LE0500 (EHV)Metallic screen and sheathnot supplied by us
Schematic cross-section of an extruded cable core, not to scale. The insulation screen is bonded in the constructions both sheets describe; LE0592S can also be the conductor screen in strippable constructions.

Both sheets describe the compound as specially designed for the semiconductive conductor screen and the bonded insulation screen. The LE0592S sheet adds that it can be used as conductor and insulation screen for bonded cable constructions, and as the conductor screen for strippable cable constructions. The LE0500 sheet does not mention strippable constructions. Neither grade is described as a strippable insulation screen. Our glossary explains bonded and strippable screens as far as the sheets describe them.

Smoothness and thermal stability

Both sheets credit the excellent distribution of carbon black and additives. For LE0592S that results in “a very smooth semiconductive screen”. LE0500 is described as a supersmooth compound with “superior smoothness”. The sheets do not give a figure for either.

Both grades are said to offer excellent thermal stability, which provides robust cable extrusion and crosslinking at high surface temperature. The LE0592S sheet adds that this allows for high cable extrusion line speed. Both sheets also mention excellent surface finish and outstanding output rates when processing conditions are optimised for the equipment and cable dimensions.

Properties side by side

Sample of black semiconductive compound pellets in a glass dish beside a sealed sample bag and a document on a clipboard
Checking a semiconductive compound sample against its documents (illustration).

The typical values in the table differ in a few places:

  • Density: 1135 kg/m³ (LE0592S) and 1120 kg/m³ (LE0500).
  • MDR max: 12 dNm and 14 dNm (ISO 6502).
  • Moisture content: < 200 ppm and < 100 ppm, measured at time of production (ISO 15512).
  • Ageing: the two sheets use different conditions. LE0592S gives < 25 % change of tensile properties after 135 °C for 240 h; LE0500 gives < 20 % after 135 °C for 168 h. Because the test durations differ, the two figures are not directly comparable.

They match elsewhere: tensile strain at break > 150 % and tensile strength > 15 MPa (25 mm/min), hot set < 100 % elongation under load and < 10 % permanent deformation (200 °C, 0.20 MPa), and DC volume resistivity < 100 Ω·cm at 23 °C and < 1000 Ω·cm at 90 °C (ISO 3915). LE0500 also lists < 100 Ω·cm at 23 °C to ASTM D991. The mechanical and hot-set values are measured on crosslinked specimens.

Standards

Both sheets list the same three: IEC 62067, AEIC CS9 and ANSI/ICEA S-108-720. Both state that the grade is expected to meet the applicable requirements included in those standards, provided it is processed using sound material handling and processing practices as well as appropriate testing procedures, and both tie that statement to the maximum recommended voltage level of the grade’s stated application, noting that some standards may cover wider voltage ranges. The LE0500 sheet’s application states no upper voltage limit. For how IEC 62067 relates to IEC 60840, see IEC 60840 vs IEC 62067.

Processing, drying and storage

The processing guidance is close to identical. All material handling should be conducted in closed systems and in clean room conditions, and a screen-pack on the extruder is recommended for improved melt homogenisation. Both list a typical melt temperature of 120 – 135 °C and a typical drying temperature of 60 °C, with a footnote of 4 h with dehumidified air. Only the LE0592S text adds an explicit recommendation to dry the compound before extrusion.

Both ship in Smallbins and state a shelf life of 18 months from production date in unopened original packages, under dry and clean conditions at 10 – 30 °C. Both recommend first-in, first-out stock rotation. Our storage guide compares these terms with the insulation grades.

Screens and insulation in the same band

LE0592S sits in the same voltage band as our HV insulation grades LE4244S and LS4201S, and LE0500 in the same band as LE4244EHV and LS4201EHV. The data sheets do not recommend a particular screen–insulation combination. Each sheet says its information relates exclusively to that product when not used with other materials, except as provided for in its test methods, and Borealis accepts no liability for use in conjunction with other products. Testing the products for suitability for a particular purpose is the customer’s responsibility.

What about HVDC?

LE0550DC is a supersmooth semiconductive compound intended for the semiconductive screens of XLPE HVDC cables; its sheet describes it for the conductor screen and insulation screen of HVDC power cables. It lists IEC 62895 and CIGRE TB 852 and gives no voltage rating. Its typical values include a density of 1075 kg/m³, MDR max 11 dNm, moisture content 100 ppm and a melt temperature of 120 – 130 °C. We supply no HVDC insulation grade.

Supply from Shanghai

We supply LE0592S, LE0500 and LE0550DC. Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and COA on request; we confirm availability of a given grade when you inquire. See our quality practice and the semiconductive screen overview. Tell us your voltage class, cable construction and volume and we will confirm availability and send the current data sheets.

References

See also