Conductor screen vs insulation screen in HV cables
The conductor screen and the insulation screen are the two semiconductive layers of an extruded HV cable. The conductor screen sits on the conductor, under the insulation; the insulation screen covers the outside of the insulation. Both are polymer loaded with carbon black, and both smooth the electric field at an interface, so that the field in the XLPE insulation between them stays even. North American documents usually call them the conductor (or strand) shield and the insulation shield.
The four core layers
Strip back a modern HV cable and you find a set of concentric extruded layers, not a single lump of plastic. From the centre out: the copper or aluminium conductor carries the current; the semiconductive conductor screen smooths the field at the rough conductor surface; the XLPE insulation holds back the voltage; and the semiconductive insulation screen gives the outside of the insulation a smooth, uniform boundary. Outside the core sit the metallic screen and sheath, which we do not supply.
Conductor screen
A stranded conductor has an uneven, bumpy surface. Without a screen, those bumps would concentrate the electric field and start partial discharge that eats into the insulation. The conductor screen covers them with a smooth equipotential surface, so the insulation sees an even field from the inside.
The field is strongest here, at the inner surface of the insulation. IEC 60840 shows it in its prequalification rule: the test is required where the calculated nominal stress is above 8.0 kV/mm at the conductor screen, against 4.0 kV/mm at the insulation screen. More on that rule in IEC 60840 vs IEC 62067.
Insulation screen
The insulation screen gives the outside of the insulation the same smooth, equipotential boundary, so the field leaves the dielectric evenly. It comes in two forms. A bonded insulation screen is fully adhered to the insulation; a strippable one is peeled off for jointing. The conductor screen is bonded to the insulation in both cases. See bonded and strippable screens in our glossary.
Side by side
| Conductor screen | Insulation screen | |
|---|---|---|
| Position | Over the conductor, under the insulation | Over the insulation, under the metallic screen |
| Job | Smooths the field at the rough conductor surface | Gives the outside of the insulation a smooth boundary |
| IEC 60840 prequalification trigger | Calculated stress above 8.0 kV/mm | Calculated stress above 4.0 kV/mm |
| Bond to the insulation | Bonded | Bonded or strippable |
| Other names | Conductor shield, strand shield | Insulation shield |
| Borlink™ grades we supply | LE0592S (HV AC), LE0500 (EHV AC), LE0550DC (HVDC) | LE0592S and LE0500 for bonded screens, LE0550DC for HVDC |
Why the interface matters
A flaw at the screen-to-insulation interface concentrates the electric field, so the two must bond with no trapped air. That is why the conductor screen, insulation and insulation screen are triple-extruded in a single pass and cross-linked together, and why the cable maker qualifies the screen and insulation combination as a whole.
What the data sheets give
The three Borlink™ screen sheets give a typical DC volume resistivity below 100 Ω·cm at 23 °C and below 1000 Ω·cm at 90 °C. The four insulation sheets give above 10 PΩ·cm at 23 °C, so the gap between the layers is enormous. Smoothness is described in words, not measured: LE0500 and LE0550DC are called supersmooth, and LE0592S is said to give a very smooth screen. The figures are typical values from the producer’s data sheets, not specifications.
We supply both layers
Insulation is a clean, natural compound; screens are carbon-black-loaded semiconductive compounds. They are different materials for different jobs, but they must be compatible at the interface. We supply Borlink™ grades for both roles across HV and EHV. The data sheets do not recommend a particular screen–insulation combination; choosing and qualifying the pair is the cable maker’s job. None of the grades we supply is described as a strippable insulation screen. For how the two AC screens differ, see LE0592S vs LE0500. Tell us your voltage class and cable construction and we will send the current data sheets.
References
- PDF · Borlink™ LE0592S product data sheet · Borealis, Ed.5, 6 Mar 2026
- PDF · Borlink™ LE0500 product data sheet · Borealis, Ed.4, 6 Mar 2026
- PDF · Borlink™ LE0550DC product data sheet · Borealis, Ed.1, 7 Apr 2026
- PREVIEW · IEC 60840:2020/AMD1:2023 preview (SIST) · Replacement text of clause 13.1, stress at the conductor and insulation screens
- PATENT · US 7,390,970 B2, Cable semiconducting shield · Names the layers conductor or strand shield and insulation shield
- VIDEO · HV XLPE underground cable construction explained · Layer-by-layer walkthrough
- WIKI · High-voltage cable · Construction background
Related products
- Borlink™ LE0592S · Semiconductive
- Borlink™ LE0500 · Semiconductive
- Borlink™ LE0550DC · Semiconductive
- Borlink™ LE4244S · Insulation
- Borlink™ LE4244EHV · Insulation