Voltage class · HV

220 kV / 230 kV cable insulation & semiconductive compounds

For 220 and 230 kV, the Borlink™ grades are LE4244S or LS4201S insulation and the LE0592S screen; the cable maker selects and qualifies the pair. This class sits at the top of the Borlink™ HV band, AC cables rated up to 230 kV (Um = 245 kV), but above the 150 kV line where IEC 62067 takes over from IEC 60840. Check your Um, the single-core scope of IEC 62067, and your insulation wall against your line, then send us your cable design, grade and volume. We supply all three grades; core grades are held in our Shanghai warehouse.

Grades for 220 kV cables

LayerGradeNotes
XLPE insulation Borlink™ LE4244S Very low sagging — horizontal lines and thick CCV walls
XLPE insulation Borlink™ LS4201S Excellent scorch resistance; reduced degassing burden
Conductor & bonded insulation screen Borlink™ LE0592S Very smooth screen; also the conductor screen in strippable constructions

Choosing between the insulation grades: LE4244S has very low sagging properties and is specially designed for extrusion on horizontal lines and for thick insulation walls on CCV lines. LS4201S is based on Supercure technology, and its sheet separately lists very good electrical performance, excellent scorch resistance for long production runs and high productivity from a reduced degassing burden. Horizontal lines or thick CCV walls point to LE4244S; long runs or a lighter degassing burden point to LS4201S. Compare them in LE4244S vs LS4201S.

All four insulation sheets state superclean insulation, assured through the Borealis Quality Management system. More on XLPE insulation and semiconductive screens.

220 kV at a glance

Rated voltage U (phase to phase)220 kV (230 kV in the other IEC 60038 series; 225 kV on French projects)
Highest system voltage Um245 kV, the figure printed on the HV data sheets
Cable test standardIEC 62067: above 150 kV (Um = 170 kV) up to and including 500 kV (Um = 550 kV)
Constructions coveredSingle-core cables only; not submarine cables
Borlink™ bandHV AC: rated up to 230 kV (Um = 245 kV)
Grades we supply LE4244S, LS4201S, LE0592S

Which standard applies

IEC 62067 applies to this class. Two dividing lines matter here: the cable test standards split at 150 kV, the Borlink™ data sheets at 230 kV. A 220 or 230 kV cable therefore falls under IEC 62067, yet within the stated application of the HV grades. IEC 62067:2022 applies to single-core cables only.

Standards listed under “Specifications” on each data sheet:

GradeStandards listed
LE4244S IEC 62067, IEC 60840, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1
LS4201S IEC 62067, IEC 60840, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1
LE0592S IEC 62067, AEIC CS9, ANSI/ICEA S-108-720

The LS4201S and LE0592S sheets say the grade “is expected to meet the applicable requirements” of the listed standards, provided it is processed using sound material handling and processing practices and appropriate testing procedures; the LE4244S sheet lists its standards without that sentence. The HV sheets apply these listings only up to their stated limit of 230 kV (Um = 245 kV), although some standards may cover wider voltage ranges. See also our quality & standards page.

What to check

System voltage and Um

Nominal voltageUmBasis
220 kV245 kVIEC 60038; VDE FNN for Central Europe
230 kV245 kVIEC 60038; PJM operating range 220–242 kV
225 kVnot givenFrench projects in CIGRE Table G2
220 kV (China)252 kVGB/T 18890.2-2015 title

Labels differ: Germany’s Bundesnetzagentur places 220 kV in its 220–380 kV extra-high-voltage network and NEETRAC’s North American survey grouped EHV as 230–400 kV, but the Borlink™ bands follow the limits on the sheets, so a 220 or 230 kV cable with Um up to 245 kV stays in the HV band.

The HV sheets bound their application by rated voltage and Um together: up to 230 kV (Um = 245 kV). China’s GB/T 18890 is titled for Um = 252 kV, which the sheets do not mention. For a GB/T 18890 design, or any system whose Um is above 245 kV or not stated, contact us for project-specific standards.

Design and testing

  • Insulation wall. ABB’s land cable guide (rev. 5, 2010) lists single-core 220 kV cables with 24.0 mm of insulation at 500 mm² and 23.0 mm from 630 to 2500 mm². These are indicative, non-binding data, so size the wall from your own design.
  • Your line. Maillefer specifies its EPL 50 Extend catenary line for 10–220 kV with 3.4–25 mm of insulation, and warns that if the viscosity near the conductor drops, “significant drooping occurs and the insulation will be off-centered”. For thick walls on CCV lines, see LE4244S above.
  • Your own testing. Each sheet describes its grade used alone and leaves suitability testing to the customer.

How to inquire

Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and COA on request: short lead times, no waiting for a production run. We confirm availability of a given grade when you inquire. What each data sheet says on shelf life and storage is in our storage guide.

Tell us your cable design, grade and volume, and we reply with availability, data sheets and pricing. Request a quote →

Installed 220–225 kV XLPE cables

  • Lübeck–Siems, Germany: 220 kV, 10.2 km, 1200 mm² Cu, XLPE, 2004.
  • Shellybanks, Dublin: 220 kV, 14 km, 1600 mm² Cu, XLPE, 1997.
  • Pioltello, Milan: 220 kV, 3 + 3 km, 1600 mm² Al, XLPE, 2005.
  • Avenir–Sausset, Île-de-France: 225 kV, 17.9 km, 1200 mm² Cu, XLPE, 2001.

Shown to illustrate the voltage class, not projects supplied by Lexin.

Further reading

Building an HVDC link? Borlink™ LE0550DC is a semiconductive compound for XLPE HVDC cable screens; its data sheet lists IEC 62895 and CIGRE TB 852 and states no voltage rating.

References