Voltage class · EHV
400 kV / 500 kV cable insulation & semiconductive compounds
For 500 kV (Um = 550 kV) and the 380/400 kV class below it (Um = 420 kV), the Borlink™ grades are LE4244EHV or LS4201EHV insulation and the LE0500 screen; the cable maker selects and qualifies the pair. Both are rated above 230 kV, within the stated application of the Borlink™ EHV grades we supply. IEC 62067 is the cable test standard, and 500 kV is its upper limit. Check your Um, prequalification, the utility specification and your insulation wall against your line, then send us your cable design, grade and volume.
Grades for 500 kV cables
| Layer | Grade | Notes |
|---|---|---|
| XLPE insulation | Borlink™ LE4244EHV | Very low sagging — horizontal lines and thick CCV walls |
| XLPE insulation | Borlink™ LS4201EHV | Excellent scorch resistance; reduced degassing burden |
| Conductor & bonded insulation screen | Borlink™ LE0500 | Supersmooth screen; robust extrusion at high surface temperature |
Choosing between the insulation grades: LE4244EHV has very low sagging properties and is specially designed for extrusion on horizontal lines and for thick insulation walls on CCV lines. LS4201EHV is based on Supercure technology, and its sheet separately lists very good electrical performance, excellent scorch resistance for long production runs and high productivity from a reduced degassing burden. Horizontal lines or thick CCV walls point to LE4244EHV; long runs or a lighter degassing burden point to LS4201EHV. Compare them in LE4244EHV vs LS4201EHV.
All four insulation sheets state superclean insulation, assured through the Borealis Quality Management system. More on XLPE insulation and semiconductive screens.
500 kV at a glance
| Rated voltage U (phase to phase) | 500 kV (380/400 kV is the class below) |
|---|---|
| Highest system voltage Um | 550 kV; an IEC 60038 note says 525 kV is also used |
| Cable test standard | IEC 62067, up to and including 500 kV (Um = 550 kV), its upper limit |
| Constructions covered | Single-core cables only |
| Borlink™ band | EHV AC: rated above 230 kV |
| Grades we supply | LE4244EHV, LS4201EHV, LE0500 |
Which standard applies
IEC 62067 applies to this class. Its scope runs up to and including 500 kV (Um = 550 kV). ABB’s 2010 guide gives ANSI/ICEA S-108-720’s range as above 46 through 345 kV; we could not confirm the current scope, so check the edition your specification names.
Every data sheet on this page lists IEC 62067, AEIC CS9 and ANSI/ICEA S-108-720 under “Specifications”.
The LE0500 sheet says the grade “is expected to meet the applicable requirements” of the listed standards, provided it is processed using sound material handling and processing practices and appropriate testing procedures; the LE4244EHV and LS4201EHV sheets list their standards without that sentence. The EHV sheets apply these listings only up to the sheet’s recommended maximum voltage, although some standards may cover wider voltage ranges; they give no upper voltage figure. See also our quality & standards page.
What to check
System voltage and Um
| Nominal voltage | Um | Basis |
|---|---|---|
| 380 kV | 420 kV | VDE FNN for Central Europe |
| 400 kV | 420 kV | National Grid TS1; IPTO TD-102/3 |
| 500 kV | 550 kV | IEC 62067; GB/T 22078.2-2008; PJM operates up to 550 kV |
| — | 525 kV | IEC 60038 note: “also used” |
Systems in this class include 500 kV in the US Western Interconnection and in China, and 400 kV in India and the London Power Tunnels. India’s 765 kV AC lines are beyond this class.
Above 245 kV, IEC 60038 lists only highest voltages for equipment, among them 420 and 550 kV. IEC 62067 stops at 500 kV (Um = 550 kV), while the EHV data sheets state only “above 230 kV”. For systems beyond 500 kV, contact us for project-specific standards.
Design and testing
- Prequalification. Allow for it in the schedule. On CIGRE’s advice, IEC 62067’s first edition introduced the prequalification (PQ) test, a long-term accelerated ageing test of the complete system of cable, joints and terminations. KEMA Laboratories described the 2011-edition test as about 100 m of cable with at least one of each accessory, a one-year (8,760 h) heating-cycle voltage test of at least 180 cycles of 24 h or more, then a lightning impulse test and an examination. A later extension-of-prequalification test takes about a quarter of the time.
- Utility specification. Read it before choosing a grade. Greece’s IPTO (TD-102/3, 2017), for example, specifies its single-core 400 kV XLPE cable to IEC 62067 at 230/400 (420) kV, with “super clean” XLPE insulation, triple-extruded semi-conducting layers and an IEC 62067 clause-13 PQ certificate as a prerequisite. The Borlink™ data sheets do not reference TD-102/3.
- Insulation wall. ABB’s land cable guide (rev. 5, 2010) lists single-core 500 kV cables with 34.0 mm of insulation at 800 mm² and 31.0 mm from 1200 to 2500 mm², and 400 kV cables with 32.0 mm at 630 mm² and 27.0 mm from 1200 mm². These are indicative, non-binding data, so size the wall from your own design.
- Your line. Maillefer’s EPL 50 Explore catenary line covers 66–500 kV with up to 32 mm of insulation; its vertical lines, with a 100 m tower, take 3.4–35 mm. On those figures a 34.0 mm wall is beyond that catenary line but within the vertical range. None of the Borlink data sheets we supply mentions vertical lines.
- Your own testing. Each sheet describes its grade used alone and leaves suitability testing to the customer.
How to inquire
Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and COA on request: short lead times, no waiting for a production run. We confirm availability of a given grade when you inquire. What each data sheet says on shelf life and storage is in our storage guide.
Tell us your cable design, grade and volume, and we reply with availability, data sheets and pricing. Request a quote →
Installed 380–500 kV XLPE cables
- Tehachapi Renewable Transmission Project (SCE), Chino and Chino Hills, California: the first North American 500 kV XLPE installation, 3.7 miles (6 km) underground, commissioned October 2016.
- Shin-Toyosu (TEPCO): 500 kV, 39.8 km, two circuits, 27 mm of insulation on a 2500 mm² conductor, in operation since 2000. CIGRE WG B1.07 describes it as the first long-distance 500 kV XLPE line.
- Berlin Diagonal, Germany: 380 kV, 1600 mm² Cu, XLPE, tunnel, 1998/2000.
- Copenhagen Metropolitan Power Project: 400 kV, 1600 mm² Cu, XLPE, 1997/1999.
- Turbigo–Rho, Milan: 380 kV, 8.4 km, 2000 mm² Cu, XLPE, 2006.
Shown to illustrate the voltage class, not projects supplied by Lexin.
Further reading
- Choosing XLPE insulation for 500 kV EHV cables
- Why superclean insulation matters at 220 kV and above
- Prequalification under IEC 62067
- HV or EHV version? How the EHV grades compare
- Triple extrusion, defined
Building an HVDC link? Borlink™ LE0550DC is a semiconductive compound for XLPE HVDC cable screens; its data sheet lists IEC 62895 and CIGRE TB 852 and states no voltage rating.
References
- DATA SHEETS · LE4244EHV Ed.4 · 2026-03, LS4201EHV Ed.3 · 2026-05, LE0500 Ed.4 · 2026-03 · Borealis
- STANDARD · IEC 62067:2022 · upper limit
- STANDARD · IEC 62067 Ed.3.0 preview · 500 kV, PQ
- STANDARD · IEC 60038 Ed.7.1 · 525 kV note
- PAPER · KEMA Laboratories, Jicable’15
- SPEC · IPTO TD-102/3
- STUDY · VDE FNN (2019) · 380 kV
- STANDARD · National Grid TS1 · 400 kV
- STANDARD · PJM design criteria · 500 kV
- STANDARD · GB/T 22078.2-2008
- WIKI · Electric power transmission · Western Interconnection
- PAPER · China EPRI (Zhou) · 500 kV lines
- WIKI · Electricity sector in India
- WIKI · London Power Tunnels
- NEWS · T&D World, SCE 500 kV
- REPORT · CIGRE WG B1.07 · Table G2, Shin-Toyosu
- GUIDE · ABB XLPE Land Cable Systems User’s Guide, 2GM 5007 GB rev. 5 (2010) · p.6; Tables 31–32
- EQUIPMENT · Maillefer catenary lines
- EQUIPMENT · Maillefer vertical lines