Choosing XLPE insulation for 500 kV EHV cables

· Updated · Selection

For AC cables rated above 230 kV, including 500 kV, we supply two superclean Borlink™ insulation grades, and their data sheets stress different things. LE4244EHV has very low sagging properties and is specially designed for extrusion on horizontal lines and for cables with thick insulation walls extruded on CCV lines. LS4201EHV, a Supercure grade with excellent scorch resistance enabling long production runs, is specially designed for high productivity due to a reduced degassing burden. Its sheet also lists very good electrical performance and does not mention sagging. So start from what limits your line: sag on a thick wall points to LE4244EHV, run length or degassing burden to LS4201EHV.

Why cleanliness decides EHV performance

A 110 kV cable and a 500 kV cable have the same layers in the same order, though the 500 kV wall is about twice as thick. As the rated voltage climbs, so do the electric field the insulation must hold back and the penalty for any imperfection in the wall. At extra-high voltage (EHV, above 230 kV) a single microscopic contaminant, void or gel can concentrate the local electric field more severely than it would at 110 kV. Over years, that stress can seed an “electrical tree” that grows through the insulation until the cable fails. This is why EHV cables are insulated with superclean XLPE grades, whose cleanliness level the producer assures through its quality management system.

Both grades here are superclean and the sheets publish no cleanliness figure, so cleanliness does not separate them. What you control is handling. The sheets call for careful, very clean handling, with material handling in closed systems and clean-room conditions (the LE4244EHV sheet says “preferably”). Dust picked up during careless handling or open storage can undo the cleanliness the producer built in, which is why stock we hold stays sealed in its original packaging until dispatch.

Sag on a thick wall

A 500 kV core can carry an insulation wall more than 25 mm thick: Shin-Toyosu, on the 500 kV page, uses 27 mm. Before the polyethylene is cross-linked, a wall that heavy can sag under gravity and drift off-centre, which can leave the wall eccentric and the field uneven.

This is the case the LE4244EHV sheet speaks to: very low sagging properties, and a design for horizontal lines and for thick insulation walls on CCV (catenary continuous vulcanisation) lines. It gives no sag measurement and does not say how the low sagging is achieved. The LS4201EHV sheet does not mention sagging and names no line type.

What we supply for 330–500 kV

Alongside the two insulation grades we supply the EHV semiconductive screen LE0500, which sits in the same voltage band. The data sheets do not recommend a particular screen–insulation combination; the cable maker selects and qualifies the combination for triple extrusion.

How to decide

Start from each sheet’s stated focus:

  • LE4244EHV first if you run a horizontal line, or thick insulation walls on a CCV line, and sag is your main concern. Those are the conditions its sheet names. It gives a shelf life of 12 months from production date in unopened original packages, dry and clean, at 10–35 °C.
  • LS4201EHV first if long production runs or the degassing burden matter most. Its sheet names no line type and does not mention sagging. It also has no packaging and storage section (Ed.3), so ask us before you plan long storage.
  • Both on trial if both concerns apply.

Both sheets state superclean insulation and list the same three standards (IEC 62067, AEIC CS9 and ANSI/ICEA S-108-720), so neither point separates the grades. Neither gives a sag measurement, a scorch-time value or degassing times, and both make it the customer’s responsibility to test the material for its own purpose. Your own trial settles the choice. The two EHV insulation grades are compared side by side here. Tell us your voltage class, line type and volume and we will confirm availability and send the current data sheets.