Voltage class · HV

110 kV / 132 kV cable insulation & semiconductive compounds

For 110 kV and its neighbours, 115, 132 and 138 kV, the Borlink™ grades are LE4244S or LS4201S insulation and the LE0592S screen; the cable maker selects and qualifies the pair. All four voltages sit inside the stated application of these Borlink™ HV grades, and IEC 60840 is the cable test standard. Check your Um, whether the design needs prequalification, and your insulation wall against your line, then send us your cable design, grade and volume. We supply all three grades; core grades are held in our Shanghai warehouse.

Grades for 110 kV cables

LayerGradeNotes
XLPE insulation Borlink™ LE4244S Very low sagging — horizontal lines and thick CCV walls
XLPE insulation Borlink™ LS4201S Excellent scorch resistance; reduced degassing burden
Conductor & bonded insulation screen Borlink™ LE0592S Very smooth screen; also the conductor screen in strippable constructions

Choosing between the insulation grades: LE4244S has very low sagging properties and is specially designed for extrusion on horizontal lines and for thick insulation walls on CCV lines. LS4201S is based on Supercure technology, and its sheet separately lists very good electrical performance, excellent scorch resistance for long production runs and high productivity from a reduced degassing burden. Horizontal lines or thick CCV walls point to LE4244S; long runs or a lighter degassing burden point to LS4201S. Compare them in LE4244S vs LS4201S.

All four insulation sheets state superclean insulation, assured through the Borealis Quality Management system. More on XLPE insulation and semiconductive screens.

110 kV at a glance

Rated voltage U (phase to phase)110 kV (115 kV in the other IEC 60038 series)
Highest system voltage Um123 kV (IEC 60038 Table 4)
Cable test standardIEC 60840: above 30 kV (Um = 36 kV) up to and including 150 kV (Um = 170 kV)
Constructions coveredSingle-core and individually screened three-core cables; not submarine cables
Borlink™ bandHV AC: rated up to 230 kV (Um = 245 kV)
Grades we supply LE4244S, LS4201S, LE0592S

Which standard applies

IEC 60840 applies to this class. It allows type approval of a complete cable system, of cables alone or of accessories alone, and adds a prequalification (PQ) test of the cable system for highly stressed designs. IEC 60840:2020 is Edition 5.0; the consolidated Edition 5.1 (2023) adds Amendment 1:2023 and its 2025 corrigendum.

Standards listed under “Specifications” on each data sheet:

GradeStandards listed
LE4244S IEC 60840, IEC 62067, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1
LS4201S IEC 60840, IEC 62067, AEIC CS9, ANSI/ICEA S-108-720, HD 632 S1
LE0592S IEC 62067, AEIC CS9, ANSI/ICEA S-108-720; IEC 60840 not listed

The LS4201S and LE0592S sheets say the grade “is expected to meet the applicable requirements” of the listed standards, provided it is processed using sound material handling and processing practices and appropriate testing procedures; the LE4244S sheet lists its standards without that sentence. The HV sheets apply these listings only up to their stated limit of 230 kV (Um = 245 kV), although some standards may cover wider voltage ranges. See also our quality & standards page.

What to check

System voltage and Um

Nominal voltageUmBasis
110 kV123 kVIEC 60038; VDE FNN for Central Europe
115 kV123 kVIEC 60038; PJM operating range 109–121 kV
132 kV145 kVIEC 60038; National Grid TS1
138 kV145 kVIEC 60038; PJM operating range 131–145 kV
150 kV170 kVNon-preferred in IEC 60038; top of IEC 60840
110 kV (China)126 kVGB/T 11017.2-2024 title

Systems in this class include Germany’s 110 kV network, North American subtransmission at 115 or 138 kV, and 110 or 132 kV connections for 50–150 MW projects in Queensland (Powerlink).

In IEC 60038, 110 kV pairs with 123 kV and 132 kV with 145 kV, and a country should use only one of the two, so a 132 kV cable is a different Um class from a 110 kV cable. Every row still sits inside IEC 60840 and inside the HV sheets’ stated application, up to 230 kV (Um = 245 kV).

Design and testing

  • Prequalification. Calculate your stresses first. Under Amendment 1, PQ is required where the calculated nominal stress exceeds 8.0 kV/mm at the conductor screen and/or 4.0 kV/mm at the insulation screen, unless, for example, the same construction with accessories of the same family is already prequalified at an equal or higher rated voltage. For 66–132 kV XLPE cables, the UK’s BS 7912:2012+A1:2017 refers to the IEC 60840:2011 PQ test above the same stresses and notes that its cable systems do not normally have such high stresses.
  • Insulation wall. ABB’s land cable guide (rev. 5, 2010) lists single-core 110 kV cables with 16.0 mm of insulation at 185 mm² and 13.0 mm from 400 to 2500 mm², and 132 kV cables with 18.0 and 15.0 mm at the same sizes. These are indicative, non-binding data, so size the wall from your own design.
  • Your line. The wall has to fit your line’s range. Maillefer, for example, specifies its EPL 50 Enter catenary (CCV) line for 10–110 kV cables with 3.4–21 mm of insulation.
  • Screen listing. IEC 60840 appears on the two insulation sheets, not on LE0592S. If your specification needs it on the screen as well, raise it when you inquire.
  • Your own testing. Each sheet describes its grade used alone and leaves suitability testing to the customer.

How to inquire

Core grades are held in our Shanghai warehouse in original sealed packaging, with batch traceability and COA on request: short lead times, no waiting for a production run. We confirm availability of a given grade when you inquire. What each data sheet says on shelf life and storage is in our storage guide.

Tell us your cable design, grade and volume, and we reply with availability, data sheets and pricing. Request a quote →

Installed 132–150 kV XLPE cables

  • Radsted–Rødby, Denmark: 132 kV, 25 km, 630 mm² Al, XLPE, 1999.
  • Radsted–Vantore Str., Denmark: 132 kV, 18 km, 1200 mm² Al, XLPE, 2002.
  • Koksijde–Slijkens, Belgium: 150 kV, 30 km, 2000 mm² Al, XLPE, 2006.
  • Tihange–Avernas, Belgium: 150 kV, 30 km, 2000 mm² Al, XLPE, double circuit, 2003.

Shown to illustrate the voltage class, not projects supplied by Lexin.

Further reading

Building an HVDC link? Borlink™ LE0550DC is a semiconductive compound for XLPE HVDC cable screens; its data sheet lists IEC 62895 and CIGRE TB 852 and states no voltage rating.

References

Other voltage classes

220 kV · 330 kV · 500 kV · All products